Skip to main content
ABB 1SFA897115R7001 — Soft Starters

ABB PSE370 Soft Starter 1SFA897115R7001, 208-600V AC, Modbus

MPN1SFA897115R7001
Active

ABB PSE370 soft starter, 1SFA897115R7001, soft start with torque control, 208...600 V AC, Modbus-RTU, 0...30 s ramp, current production.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

1SFA897115R7001 key specifications
ParameterValue
Terminal typeMain Circuit: Bars
Product main typePSE370
Voltage208 ... 600 V AC
Initial voltage during start30 ... 70 %
Step down voltage special rampNo %
Rated control supply voltage100 ... 250 V AC
Rated control circuit voltage24 V DC
Technical UL (CSA, maximum operating voltage UL, CSA)Main Circuit 600 V
Current limit function1.5 ... 7xIe
Starting capacity at maximum rated current ie4xIe for 10s
Rated operational current - In-Line connection370 A
Technical UL (CSA, horsepower rating UL, CSA)(200 ... 208 V AC) Three Phase 125 Hp
All specifications+37
1SFA897115R7001 additional specifications
ParameterValue
Rated operational power - In-Line connection(230 V) 110 kW
Rated frequency50/60 Hz
IP ratingacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
ProtocolModbus-RTU
Switch for inside delta connectionNo
Popular downloads (CAD dimensional drawing)2CDC001079B0201
Material compliance (Toxic substances control act - TSCA)2CMT2023-006524
Material compliance (Conflict minerals reporting template)9AKK108467A5658
Technical UL (CSA, tightening torque UL, CSA)Control Circuit 4.4 in·lb
FunctionSoft start with torque control
Ramp time0 ... 30 second [unit of time]
Analog outputs4...20 mA
Run signal relayYes
Tightening torqueControl Circuit 0.5 N·m
Fault signal relayYes
Overload protectionBuilt-in electronic overload protection
Protection functionElectronic overload protection, EOL; Locked rotor protection; Current underload protection
By-pass signal relayYes
Overload signal relayYes
Ambient air temperatureOperation -25 ... +60 °C
Service factor percentage100 %
Object classification codeQ
Popular downloads (EPLAN data)9AAC170228_EPLAN
Signal indication faultRed
Integrated electronic overloadYes
Connecting capacity main circuitHole Diameter 8.5 mm
Signal indication running rGreen
Connecting capacity supply circuitRigid 1 x 2.5
IDEA granular category code4740 >> Soft starter
Signal indication protectionYellow
Connecting capacity control circuitRigid 1 x 2.5 mm²
Signal indication ramping up (Down)Green
Popular downloads (Instructions and manuals)1SFC132427M0201
Signal indication completed start rampGreen
Popular downloads (Data sheet, technical information)1SFC132012C0201
Popular Downloads/Instructions and manuals (Part 2)1SFC132057M0201
Popular Downloads/Instructions and manuals (Part 3)1SFC132060M0201

Product details

The ABB PSE370 soft starter 1SFA897115R7001 delivers soft start with torque control for three-phase induction motors, with a ramp time adjustable from 0 to 30 seconds and an initial voltage setting between 30 and 70 % of line voltage — giving you control over the acceleration profile for pump, fan, or conveyor starts without mechanical shock. Rated for 208 to 600 V AC at 50/60 Hz, it carries a control supply of 100–250 V AC and a separate 24 V DC control circuit, so it fits standard panel voltages across regions. Built-in electronic overload protection covers locked rotor, current underload, and EOL conditions, with a current limit function adjustable from 1.5 to 7 times the motor full-load current — one less external relay to wire.

Integration and communications

Modbus-RTU on the control terminals lets a PLC or HMI read run, fault, overload, and bypass status directly — three dedicated signal relays (run, fault, bypass, overload) are also available for hardwired interlocks. A 4–20 mA analog output provides a proportional motor current signal for remote monitoring or trending. Main circuit connections are via bars with an 8.5 mm hole diameter; control wiring accepts 1 x 2.5 mm² rigid, tightened to 0.5 N·m. The main terminals are IP00 per IEC 60529, so it lives inside a panel — not outdoors.

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, classified as B2B WEEE Category 5 (Small Equipment).

Frequently asked questions

What is 1SFA897115R7001's listed function?

Its function is soft start with torque control, meaning it ramps motor voltage up gradually while managing torque to reduce mechanical stress and inrush current.

What is 1SFA897115R7001's listed ramp time?

The ramp time is adjustable from 0 to 30 seconds, letting you tailor the acceleration profile to the load.

MPN
1SFA897115R7001