Skip to main content
Siemens 3RA6120-2AP32

Siemens 3RA6120-2AP32 SIRIUS Compact Starter, 53 kA at 400 V

MPN 3RA6120-2AP32
Active

Siemens SIRIUS 3RA6120-2AP32 compact direct starter, 53 kA breaking capacity at 400 V, 90 W motor rating at 400 V, 110–240 V AC/DC control voltage, adjustable CLASS 10/20, spring-loaded terminals, 45 mm width.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RA6120-2AP32 specifications
ParameterValue
Mountingscrew and snap-on mounting
Depth165 mm
Width45 mm
Height191 mm
Trip classCLASS 10 and 20 adjustable

Product details

53 kA at 400 V — what that means for the panel

The 3RA6120-2AP32: In a panel with a transformer-fed bus that delivers 50 kA prospective short-circuit current, this starter clears the fault without needing a current-limiting fuse ahead of it. The unit is a direct starter (non-reversing), rated for continuous operation per IEC 60947-6-2. It handles a 90 W motor load at 400 V, drawing 0.4 A at 400 V AC.

Trip class and thermal protection — adjustable CLASS 10/20

The overload relay is adjustable between CLASS 10 and CLASS 20. CLASS 10 trips in under 10 seconds at 7.2× FLC — use it for submersible pumps or compressors that need fast lock-rotor protection. CLASS 20 allows a longer start for high-inertia loads like fans or centrifuges. The setting is a simple dial on the front; no swap-out of a separate overload block. Power dissipation is 6 W AC maximum, 5.1 W DC maximum — low enough that several starters can sit side-by-side on the DIN rail without forced cooling, provided ambient stays within -20 to +60 °C during operation.

Mounting and wiring — DIN rail, spring terminals

Any mounting position is allowed, though vertical orientation on the rail is recommended for optimal heat dissipation. No screw torque to check — strip, insert, release. The control circuit uses the same spring-clamp interface.

Environmental robustness — vibration and shock

Vibration resistance tested to 10 cycles at 4–5.8 Hz with 15 mm amplitude, then 5.8–500 Hz at 20 m/s². Shock resistance is 60 m/s² (6 g) with 10 ms half-sine, three shocks per axis. This means the starter holds its settings and contact alignment on a conveyor drive or a compressor skid without nuisance trips. Storage and transport temperature range is -55 to +80 °C — the unit can sit in an unheated warehouse or truck without damage. Pollution degree 3 means it tolerates conductive dust and condensation typical of industrial enclosures.

MPN