Skip to main content
Siemens 3RV1021-0AA15

Siemens 3RV1021-0AA15 SIRIUS Motor Protection Circuit Breake

MPN 3RV1021-0AA15

Siemens SIRIUS motor protection circuit breaker, 3RV1021-0AA15, 0.16 A rated continuous current, CLASS 10 trip class, 100 kA breaking capacity at 400 V AC, screw and snap-on DIN rail mounting.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1021-0AA15 specifications
ParameterValue
Depth96 mm
Width45 mm
Height97 mm
Trip classCLASS 10

Product details

Motor protection circuit breaker, 0.16 A, CLASS 10

The Siemens 3RV1021-0AA15 is a SIRIUS motor protection circuit breaker designed for motor protection, rated at 0.16 A continuous current with a CLASS 10 trip class — meaning it will trip within 10 seconds at 7.2× rated current, sized for small fractional-horsepower motors or control transformer primaries where the inrush duration stays under that curve. Its 100 kA breaking capacity at 400 V AC (and at 240 V, 500 V, and 690 V AC) means it safely interrupts fault currents up to that level without cascading upstream — a figure that holds the unit on the grid for high-fault-capacity industrial panels, provided the upstream protective device is coordinated.

DIN rail integration and wiring

At 45 mm wide, 97 mm tall, and 96 mm deep, this breaker occupies a single 45 mm module on the DIN rail — a standard footprint for SIRIUS motor protection breakers, so it fits existing panel layouts without re-spacing. The main circuit uses screw-type terminals accepting solid conductors of 2x (0.5... 1.5 mm²) and 2x (0.75... 2.5 mm²), or stranded 2x (1... 2.5 mm²) and 2x (2.5... 6 mm²). The auxiliary switch is transverse design, with zero auxiliary contacts fitted as standard — if you need aux contacts, they are added separately. Clearance: 0 mm backwards and 0 mm at the side, so no extra air gap is required between units on the rail — you can pack them tight.

Shock resistance is 25g for 11 ms.

Auxiliary switching and contact ratings

An auxiliary switch is present (transverse design), rated at 1 A at 24 V, 0.5 A at 230 V, and 0.15 A at 60 V — these are the switching capacities for the auxiliary contact block, not the main motor circuit. Mechanical endurance of the main contacts is typically 100 000 operating cycles. Maximum switching frequency at AC-3 duty is 15 operations per hour.

MPN
3RV1021-0AA15