Skip to main content
Siemens 3RV1031-4GA10

Siemens 3RV1031-4GA10 SIRIUS Motor Protection Circuit Breake

MPN 3RV1031-4GA10

Siemens SIRIUS motor protection circuit breaker, 3RV1031-4GA10, 45 A continuous, Class 10 trip, 50 kA breaking capacity at 400 V AC, screw terminals, 55 x 140 x 149 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RV1031-4GA10 specifications
ParameterValue
Depth149 mm
Width55 mm
Height140 mm
Trip classCLASS 10

Product details

It's built for 3-phase motor circuits up to 22 kW at 400 V AC. Breaking capacity runs 100 kA at 240 V AC, 50 kA at 400 V AC, 10 kA at 500 V AC, and 4 kA at 690 V AC — so on a 400 V line you've got plenty of headroom for high-fault panels. Front IP20 keeps fingers out of the live terminals.

A slower class (e.g. Class 20) would let the motor cook longer; a faster one (Class 5) might nuisance-trip on start-up inrush. The 45 A continuous rating and 22 kW at 400 V match up with a 45–50 A motor full-load current on a 400 V supply. If your motor nameplate says 48 A FLA, this breaker is sized right.

If you're filling a BOM line or replacing a failed unit on a live panel, this is the current-production direct fit.

Zero clearance needed at the back or sides for heat dissipation. Terminals accept 2x (0.75–16 mm²) solid or 2x (0.75–25 mm²) stranded, plus a single up to 35 mm² stranded. That covers most motor circuit feeds up to around 10 mm² per phase; for larger conductors you'd step up to the next frame size. Finger-safe touch protection (IP20 front) means the panel builder doesn't need additional covers over the terminals for basic shock protection.

MPN
3RV1031-4GA10