Skip to main content
Siemens 3RW4423-3BC44

Siemens 3RW4423-3BC44 SIRIUS Soft Starter, 62 A, 230 V

MPN 3RW4423-3BC44

Siemens SIRIUS 3RW4423-3BC44 soft starter, 62 A at 40 °C, 230 V, 50/60 Hz, 3-phase, integrated bypass, box terminal main circuit, spring-loaded auxiliary terminals, screw fixing, 270 mm depth.

$2,541.27 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW4423-3BC44 specifications
ParameterValue
Mountingscrew fixing
Depth270 mm
Width170 mm
Height192 mm

Product details

62 A at 40 °C — what it means for the motor branch

The 3RW4423-3BC44: That 62 A figure is the continuous current in the bypass-closed state — the integrated bypass contactor carries the load after start, so the thyristor stack only sees starting current. For a 30 kW motor at 230 V (roughly 85 A FLA), this unit is undersized; it fits motors up to about 22 kW at 230 V where FLA lands near 60 A. The adjustable current limitation lets you cap starting current between 100% and about 400% of the motor FLA — useful for soft-starting conveyors or pumps that can't take a full-voltage jolt. Minimum load is 8%, so lightly loaded machines still get controlled acceleration without the unit dropping out.

Panel fit and wiring — what the dimensions and terminals tell you

At 270 mm deep, 170 mm wide, and 192 mm tall, this soft starter needs a back-panel clearance of 100 mm above and 75 mm below for airflow — the thyristor heat sink dumps about 30 W at rated current, so don't box it in. Side clearance is only 5 mm, so you can pack units tight horizontally. Screw fixing means four M5 bolts into the backplate — no DIN-rail clip. Main circuit uses box terminals accepting stranded 2x (4...50 mm²) — that's up to 1/0 AWG. The mounting position allows vertical surface with ±90° rotation and ±22.5° tilt front-to-back, so you can orient it for cable entry without fighting the gland plate.

Lifecycle and sourcing — still an active catalog line

No stock-holding claim here; sourced per RFQ from authorized industrial distribution.

Protection and diagnostics — what's built in

Motor overload protection is integrated — no separate thermal relay or electronic overload in the branch. The unit also has intrinsic device protection that monitors thyristor junction temperature and over-current, so a stalled rotor or phase imbalance won't take out the power stack. A display shows fault codes — no programmer needed to read the last trip cause. External reset input lets you clear faults remotely from a PLC or a pushbutton on the panel door, which saves a trip to the cabinet on a nuisance trip.

MPN