Skip to main content
Siemens 3RW4435-2BC45

Siemens 3RW4435-2BC45 SIRIUS Soft Starter, 232 A at 40 °C

MPN 3RW4435-2BC45

Siemens SIRIUS 3RW4435-2BC45 soft starter, rated 232 A at 40 °C, 690 V insulation voltage, 50…60 Hz, screw fixing, 170 x 200 x 270 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW4435-2BC45 specifications
ParameterValue
Mountingscrew fixing
Depth270 mm
Width170 mm
Height200 mm

Product details

What the 232 A rating means for your motor line

At 50 °C the output derates to 203 A; at 60 °C it drops to 173 A, so the 40 °C figure is the one to use for panel sizing unless you are in a hot cabinet. Operating frequency is 50 to 60 Hz, one part covers both.

Thyristor switching and inside-delta wiring

Thyristors handle the ramp-up and ramp-down, so there are no mechanical contacts to wear on starting duty. The part supports inside-delta circuit connection, which lets you wire the soft starter in the motor delta legs rather than in the line — this reduces the current the soft starter sees by a factor of √3, effectively extending its reach to a larger motor frame than a line-connected unit of the same amp rating. Minimum load is 8 %, so it handles lightly loaded conveyors or pumps without dropping out. Adjustable current limitation is onboard, and motor overload protection is integrated — no separate overload relay needed in most configurations.

Mounting and clearances for panel layout

The unit measures 170 mm wide by 200 mm high by 270 mm deep, and it mounts via screw fixing on a vertical surface. Clearance requirements are 100 mm above, 75 mm below, and only 5 mm at the sides — so you can pack them side-by-side in a multi-starter lineup. Main current circuit connections are busbar type; the main contact terminals accept 4 to 250 kcmil or stranded 25 to 120 mm². Auxiliary contacts take 2x (24 to 16 AWG) solid or 2x (0.25 to 1.5 mm²) solid.

MPN
3RW4435-2BC45