Skip to main content
Siemens 3RW4444-2BC34

Siemens 3RW4444-2BC34 SIRIUS Soft Starter, 433 A, 690 V

MPN 3RW4444-2BC34

Siemens SIRIUS 3RW4444-2BC34 soft starter, 433 A at 40 °C, 690 V insulation voltage, 50/60 Hz, inside-delta circuit, adjustable current limitation, motor overload protection, display for fault signal.

$8,110.22 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW4444-2BC34 specifications
ParameterValue
Mountingscrew fixing
Depth298 mm
Width210 mm
Height230 mm

Product details

Rated current and thermal derating profile

The 3RW4444-2BC34: Insulation voltage is rated 690 V at 50/60 Hz, matching standard 400/480 V motor circuits with headroom for line transients.

Inside-delta wiring and minimum load

Supports inside-delta circuit connection, which reduces the current through the thyristors to 58 % of the line current — useful for retrofitting into existing delta-wound motor starters without upsizing the soft starter. Minimum load is 8 % of the rated current — below that the thyristor firing angle may not hold conduction, so verify the motor no-load current exceeds this threshold.

Integrated protection and fault indication

Built-in motor overload protection and intrinsic device protection (over-temperature, phase imbalance) reduce external relay count; adjustable current limitation lets you set the start ramp ceiling without separate hardware. A display provides fault signal readout on the unit — no separate HMI needed for basic diagnostics.

Panel fit and connection sizing

Dimensions are 230 mm high, 210 mm wide, 298 mm deep — screw fixing to the mounting surface, with ±90° rotation and ±22.5° tilt allowance for tight enclosures. Main current circuit accepts busbar connection or cable: stranded 70–240 mm², finely stranded 50–240 mm², or AWG 2/0–500 kcmil. Auxiliary terminals take solid 0.25–1.5 mm² or AWG 24–16.

Environmental limits and pollution degree

Rated pollution degree 3 per IEC 60947-4-2, meaning it tolerates conductive dust and occasional condensation — suitable for industrial enclosures without climate control.

Current production — the 3RW4444-2BC34 is an active SIRIUS catalog item, not a legacy or phase-out line.

MPN
3RW4444-2BC34