Skip to main content
Siemens 3RW5214-3AC05

Siemens 3RW5214-3AC05 SIRIUS Soft Starter, 200-600 V

MPN 3RW5214-3AC05
Active

Siemens SIRIUS 3RW5214-3AC05 hybrid soft starter, 7.5 A minimum, 200-600 V AC, Class 10A/10E/20E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, UL/CSA/CE, screw fixing.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5214-3AC05 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Active production — what it means for your BOM line

The 3RW5214-3AC05: It is a SIRIUS-branded hybrid switching device — the product category that combines a solid-state soft starter with a bypass contactor for reduced heat dissipation during run.

Trip class and motor protection — the selection anchor

You can also set CLASS 10E or 20E via parameter — useful when starting high-inertia loads like centrifuges or large fans that need a longer ramp without nuisance tripping. Minimum settable current is 7.5 A, with a minimum load of 15% relative to the smallest settable Ie — so it handles small motors down to about 1.1 A at the low end of the adjustment range. Rated supply voltage is 200…600 V AC, covering common global line voltages from 208 V to 575 V without a tap-change transformer.

Fieldbus and control — what connects where

Onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET are all supported — the soft starter talks directly to the PLC without an external gateway. PROFIenergy is available when used with the PROFINET communication module. Analog output is configurable as 4…20 mA (default) or 0…10 V when parameterized with the High Feature HMI. Remote reset is done by cycling the 24 V DC control supply voltage. Firmware update capability is built in, and the unit logs errors to an onboard logbook when the special accessory is fitted.

Panel fit and mounting constraints

Mounts via screw fixing (not DIN rail snap-on), so budget for four screws into the backplate. Dimensions are 275 mm high, 170 mm wide, 152 mm deep — allow 100 mm clearance above, 75 mm below, 10 mm forward, and 5 mm to the side for ventilation and wiring access. Operating temperature range is -25…+60 °C, but derate above 40 °C. The unit can be tilted ±10° on a vertical surface, which helps when fitting into tight enclosures. Solid wire terminations accept 2x 1.0…2.5 mm² and 2x 2.5…10 mm² — the larger range covers the power wiring, the smaller covers control wiring.

Compliance and approvals — what the certs cover

Carries UL, CSA, and CE marking — accepted in North American and European installations without additional agency review. Shock resistance is 15 g / 11 ms, with potential contact lifting above 12 g / 11 ms. Service factor is 1.0, meaning no continuous overload margin beyond nameplate — size the motor FLA to match the soft starter setting exactly.

MPN