Skip to main content
Siemens 3RW5245-2TC04

Siemens 3RW5245-2TC04 Soft Starter, 135 A, 200-480 V, SIRIUS

MPN 3RW5245-2TC04
Active

Siemens SIRIUS 3RW5245-2TC04 soft starter, 135 A minimum, 200-480 V, Class 10A/10E/20E, PROFIBUS/Modbus RTU/TCP/EtherNet/IP/PROFINET, screw fixing, 393x210x203 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5245-2TC04 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width210 mm
Height393 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Ratings that govern the motor start

The 3RW5245-2TC04: Minimum setting current is 135 A, which sets the floor for the motor FLA you can protect — anything below that and the soft starter can't regulate the ramp. The voltage range is 200-480 V, covering common low-voltage industrial supplies from 208 V to 480 V without a tap change. Trip class is selectable: default CLASS 10A, or 10E and 20E per IEC 60947-4-2. For a pump or conveyor start that needs a longer ramp without nuisance tripping, 20E gives you the headroom; for a quick-start fan, 10A keeps the thermal protection tight.

Fieldbus options and control supply

Built-in PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — this covers the major industrial Ethernet and serial fieldbuses without an add-on module. PROFIenergy support is available when paired with the PROFINET communication module. Control supply is 24 V DC. Remote reset is possible by cycling the control supply voltage. The unit also supports auto-reset and firmware updates.

Mounting and clearances

Screw fixing with a vertical mounting surface; the unit can be rotated ±90° or tilted ±22.5° front-to-back. Required clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, 5 mm at the sides. Envelope dimensions: 393 mm high, 210 mm wide, 203 mm deep.

Approvals and compliance

CE, UL, and CSA approved. Pollution degree 3 per IEC 60947-4-2. Operating temperature range -25 to +60 °C, with derating required at 40 °C or above. Shock resistance 15 g / 11 ms.

MPN
3RW5245-2TC04