Skip to main content
Siemens 3VA1080-4ED46-0AA0

Siemens 3VA1080-4ED46-0AA0 SENTRON MCCB, 80 A, 4-Pole, 121 k

MPN 3VA1080-4ED46-0AA0
Active

Siemens SENTRON 3VA1080-4ED46-0AA0, molded case circuit breaker, 4-pole, 80 A, TM210 thermal-magnetic release, 121 kA at 240 V, IP40 front.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3VA1080-4ED46-0AA0 specifications
ParameterValue
Poles4
Depth70 mm
Width101.6 mm
Height130 mm

Product details

It handles fault currents up to 121 kA at 240 V, dropping to 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.

Thermal derating and release

That means a panel builder running this breaker in a 60 °C enclosure (common near a drive or transformer) should plan for 77 A max continuous load — not the full 80 A. The TM210 release has an adjustable magnetic trip (li) up to 800 A, so you can tune the instantaneous pickup for motor inrush or cable protection without swapping the breaker.

No communication function on this variant, no motor drive, no ground-fault monitoring — it is a straight line-protection MCCB.

MPN
3VA1080-4ED46-0AA0