Siemens 3VA1220-6EF42-0AA0

SENTRON 3VA1220-6EF42-0AA0 MCCB, 200 A, 4-Pole, TM240, 220 k

MPN 3VA1220-6EF42-0AA0
Active

Siemens SENTRON 3VA1220-6EF42-0AA0, molded case circuit breaker, 4-pole, 200 A, TM240 overload release, line protection, IP40 front.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3VA1220-6EF42-0AA0 specifications
ParameterValue
Poles4
Depth70 mm
Width140 mm
Height158 mm

Product details

At 240 V it interrupts 220 kA — that is serious fault-current headroom for high-capacity mains or subfeeds where upstream coordination demands a high SCCR. At 415 V the breaking capacity is still 154 kA, and it tapers to 17 kA at 690 V — so it stays usable on 400 V-class systems without a second tier of current-limiting fuses.

Ratings that drive the choice

At 55 °C it derates to 194 A, at 60 °C to 188 A, and at 70 °C to 176 A. If the panel sits near a heat source or in a hot plant, that derating curve tells you whether this frame size still works or you need to step up to the next amp rating. The TM240 release means the thermal element is calibrated for a 200 A frame with a 240 A fixed magnetic pickup — typical for protecting cables or busbars against overloads while clearing high-impedance faults fast. Power loss is 42 W maximum at rated current — that is heat that stays inside the enclosure.

Verify the busbar spacing and the mounting footprint against your existing panel layout; the SENTRON 3VA family uses a common bolt pattern across the frame sizes, so swapping within the family usually avoids drilling new holes.