Skip to main content
Siemens 5SL4163-7

Siemens 5SL4163-7 SENTRON MCB, 1-Pole C 63 A 10 kA

MPN 5SL4163-7
Active

Siemens SENTRON 5SL4163-7, miniature circuit breaker, 1-pole, C characteristic, 63 A, 10 kA, 400 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL4163-7 specifications
ParameterValue
Poles1
IP ratingIP20
Depth76 mm
Width18 mm
Height90 mm
Energy limitation class3

Product details

The Siemens SENTRON 5SL4163-7 is a 1-pole miniature circuit breaker with a C tripping characteristic, rated 63 A at 400 V AC. It carries a 10 kA breaking capacity under both EN 60898 and IEC 60947-2, which means it can safely interrupt fault currents up to that level on a 400 V line without upstream cascading. The C-curve trips between 5× and 10× rated current — suited for mixed resistive and moderate inductive loads like general-purpose branch circuits in residential or light commercial infrastructure.

Panel fit and integration

Occupies one modular width unit (18 mm) on standard DIN rail. Depth of 76 mm and installation depth of 70 mm leave clearance for wiring behind the gland plate. IP20 with connected conductors — protected against finger contact but not washdown; intended for enclosed distribution boards. Mounting position is any, so it can be oriented vertically or horizontally inside the panel without derating the 63 A rating.

Key ratings in context

Rated for 50/60 Hz supply. Overvoltage category III and pollution degree 2 — standard for fixed-installation distribution boards. Power loss is 5 W per pole at rated current in hot operating state, relevant for thermal budgeting inside a multi-pole enclosure. The breaker accepts supplementary devices (auxiliary contacts, shunt trips, undervoltage releases) on the side, so it can be expanded for remote signaling or emergency-off functions without swapping the base unit.

MPN
5SL4163-7