Skip to main content
Siemens 5SL6250-6RC

Siemens 5SL6250-6RC SENTRON MCB, 50 A, 2-pole, B-curve, 7.5

MPN 5SL6250-6RC
Active

Siemens SENTRON 5SL6 series, 5SL6250-6RC, miniature circuit breaker, 50 A, 2-pole, B characteristic, 7.5 kA breaking capacity per EN 60898, 415 V AC rated.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL6250-6RC specifications
ParameterValue
Poles2
IP ratingIP20
Depth76 mm
Width36 mm
Height90 mm

Product details

Siemens 5SL6250-6RC — 50 A, 2-pole, B-curve MCB for residential and infrastructure panels

The Siemens 5SL6250-6RC is a 2-pole miniature circuit breaker from the SENTRON 5SL6 family, rated 50 A at 415 V AC with a B tripping characteristic and a 7.5 kA breaking capacity per EN 60898. At 36 mm wide (2 width units), it occupies two adjacent DIN-rail positions in a consumer unit or sub-distribution board.

The B characteristic (3–5× In) means this breaker will hold through the brief magnetizing inrush of a small transformer or a bank of LED drivers, but it trips faster than a C-curve on a hard short — a deliberate trade-off for circuits where the load current is predictable and the fault current path is short. For panels with a higher declared fault level, coordination with an upstream backup fuse or a current-limiting MCB is required. The 50 A rating on a 2-pole format suits sub-mains or high-current final circuits where single-pole switching is insufficient and a 2-module width is acceptable.

Panel integration — DIN-rail mount, 2-module width, any position

Mounting position is unrestricted — vertical, horizontal, or inverted — which simplifies layout in tight enclosures. Terminal capacity accepts 0.75 mm² to 25 mm², covering most final-circuit cable sizes up to 50 A.

Compliance and approvals — EN 60898, overvoltage category III, touch protection

Rated and tested per EN 60898 for the 7.5 kA breaking capacity. Overvoltage category III (distribution-board level) per IEC 60664. Touch protection is integrated — no live parts accessible with the breaker snapped onto the rail. Halogen-free and silicon-free construction, sealable for tamper-evident tagging. The 10 000 mechanical switching cycles cover typical residential and light commercial service life.

MPN
5SL6250-6RC