Skip to main content
Siemens 5SL6304-7CC

Siemens 5SL6304-7CC SENTRON MCB, 3-pole C 4A, 6kA

MPN 5SL6304-7CC
Active

Siemens SENTRON 5SL6304-7CC miniature circuit breaker, 3-pole, C-curve, 4 A, 6 kA breaking capacity at 400 V AC, 3 modular units (54 mm wide).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL6304-7CC specifications
ParameterValue
Poles3
IP ratingIP20
Depth76 mm
Width54 mm
Height90 mm
Energy limitation class3

Product details

The Siemens SENTRON 5SL6304-7CC is a 3-pole miniature circuit breaker with a C-curve trip characteristic, rated 4 A at 400 V AC. Its 6 kA breaking capacity per EN 60898 covers standard residential and light commercial infrastructure branch circuits — think lighting panels, small distribution boards, and general-purpose power feeds where fault levels stay under that threshold. C-curve means the magnetic trip fires between 5 and 10 times rated current — 20 to 40 A for this 4 A unit. That's the right match for mixed resistive and moderate inductive loads: lighting, small motors on start-up, control transformers. It won't nuisance-trip on a motor's inrush, but it clears a hard short fast enough to protect the downstream wiring.

Sizing and thermal derating

The 4 A rating holds at 30 °C ambient. Push the panel ambient to 40 °C and you're down to 3.82 A; at 50 °C it's 3.63 A. If this breaker sits in a crowded enclosure next to other heat sources, size the load against the derated figure — not the 30 °C number. The 75 °C max operating temp is the case limit, not the load-carrying limit.

Mechanical fit and panel integration

Three modular units wide at 54 mm, 76 mm deep, 90 mm tall. Snaps onto standard DIN rail in any mounting position. The 70 mm installation depth leaves room behind the rail for wiring — no tight squeeze. Spring-cage terminals accept 0.2–2.5 mm² solid or ferruled stranded; strip length 8 mm. IP20 with conductors connected — fine inside a closed panel, not for wet or dusty locations.

MPN
5SL6304-7CC