Skip to main content
Siemens 5SM1614-6

Siemens 5SM1614-6 SENTRON RCCB, 40A 300mA Type A, 2-pole

MPN 5SM1614-6

Siemens SENTRON 5SM1 series RCCB, 5SM1614-6, 2-pole, 40 A rated, 300 mA Type A residual current, 10 kA SCCR, DIN rail mount.

$175.45 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM1614-6 specifications
ParameterValue
Short circuit rating10 kA
Poles2
MountingDIN rail (REG)
Temp operating max45 °C
Temp operating min-25 °C

Product details

The Siemens 5SM1614-6 is a 2-pole residual current circuit breaker (RCCB) from the SENTRON 5SM1 series, rated 40 A at 230 V AC with a 300 mA Type A residual tripping current. Type A means it detects sinusoidal AC fault currents plus pulsating DC fault currents — the standard for circuits feeding electronic loads like VFDs, switched-mode power supplies, and lighting ballasts that generate half-wave rectified leakage. Rated short-circuit current withstand is 10 kA, and the part carries a 1 kA surge current resistance. The 2-pole body takes 2 width units on DIN rail, with a 55 mm installation depth.

Thermal derating — the real ampacity

Full 40 A rating holds at ambient up to 45 °C. Above that, derate linearly: 38.4 A at 50 °C, 36.8 A at 55 °C, 35.2 A at 60 °C, 33.6 A at 65 °C, and 32 A at 70 °C.

MPN