Siemens 5SM3412-0LB

Siemens 5SM3412-0LB SENTRON RCCB, 2-pole, 25 A, 100 mA, 230

MPN 5SM3412-0LB

Siemens SENTRON 5SM3412-0LB, RCCB, 2-pole, type AC, In: 25 A, 100 mA, Un AC: 230 V, 10 kA SCCR, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM3412-0LB specifications
ParameterValue
Short circuit rating10 kA
Poles2
MountingDIN rail (REG)

Product details

The 5SM3412-0LB: The 25 A rated current and 100 mA residual current set the protection threshold: this RCCB will trip when leakage to earth exceeds 100 mA, which is typical for general-purpose submain or feeder protection where a higher threshold avoids nuisance tripping from cable capacitance or equipment inrush. The AC-type detection (type AC) responds to sinusoidal AC residual currents only; if your load includes pulsed DC or smooth DC leakage (e.g., from VFDs, UPS, or EV chargers), you need a type A or B RCCB instead.

Mounts on DIN rail (REG) in any position. Installation depth is 70 mm, fitting standard 18 mm modular enclosures. The silicon-free construction is useful for environments where silicone outgassing can contaminate contacts or optics.

Ambient limits and service life

The 45 °C maximum limits installation in unconditioned hot attics or directly adjacent to high-heat sources without derating.

This is a current-production part (lifecycle stage: current). No official successor has been announced — the 5SM3 design remains the active SENTRON RCCB series for this rating.