Skip to main content
Siemens 5SM3444-8

Siemens 5SM3444-8 SENTRON RCCB, 40 A, 100 mA, Type A, 4-pole

MPN 5SM3444-8

Siemens SENTRON 5SM3 series, RCCB, 5SM3444-8, 4-pole, 40 A, 100 mA, Type A, 400 V AC, 10 kA, selective, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM3444-8 specifications
ParameterValue
Short circuit rating10 kA
Poles4
MountingDIN rail (REG)
Depth77 mm
Width72 mm
Height90 mm

Product details

The Siemens 5SM3444-8 is a 4-pole SENTRON residual current circuit breaker (RCCB) rated 40 A at 400 V AC, 50 Hz, with a 100 mA Type A trip characteristic. It's a selective (time-delayed) design — meaning it coordinates with downstream RCCBs so only the faulted circuit trips, keeping the rest of the distribution board live.

Thermal derating — the real-world current rating

Above that, it derates linearly: 37.6 A at 50 °C, 35.2 A at 55 °C, 32.8 A at 60 °C, 30.4 A at 65 °C, and 28 A at 70 °C.

Type A fault current and selective coordination

Type A detects sinusoidal AC residual currents and pulsating DC residual currents — the kind produced by single-phase rectifiers, switching power supplies, and variable-speed drives. The 100 mA trip threshold suits sub-distribution boards feeding socket outlets or mixed loads where a 30 mA device would nuisance-trip. The selective (S-type) design withstands a 5 kA surge current without tripping, so lightning or capacitor inrush won't drop the board.

MPN