Siemens 5SM3644-0MJ

Siemens 5SM3644-0MJ SENTRON RCCB, 40A 3+N-POL 300mA 400V 10k

MPN 5SM3644-0MJ

Siemens SENTRON 5SM3 RCCB, 5SM3644-0MJ, residual current operated circuit breaker Type AC, 40 A, 3+N-pole, 300 mA, 400 V, 10 kA, 50 Hz.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Product details

It's rated 40 A, 3+N-pole, 300 mA sensitivity, 400 V, with a 10 kA breaking capacity at 50 Hz. This is the core earth-leakage protection device for a three-phase panel — catches ground faults on the line side of the load, not the branch circuit.

40 A continuous rating means this RCCB sits upstream of loads drawing up to that current — sized for a sub-distribution board feeding several smaller circuits. The 300 mA residual sensitivity is for fire protection or equipment protection, not personnel shock protection (that's 30 mA or lower). It trips on sinusoidal AC earth faults only (Type AC); if the load has rectifiers, VFDs, or switching supplies that generate pulsed DC fault currents, you'd need Type A or Type B instead.

Deployment context

The 3+N-pole design switches all three phases plus the neutral; the neutral must pass through the device for the residual current sensing to work. Rated 50 Hz only — not suitable for 60 Hz installations or variable-frequency supplies without verifying the core's frequency response.