Skip to main content
Siemens 5SU1354-1LB20

Siemens 5SU1354-1LB20 SENTRON RCBO, 2-pole 1P+N, 20 A, Type

MPN 5SU1354-1LB20

Siemens SENTRON 5SU1354-1LB20 RCBO, 2-pole 1P+N, rated current 20 A, tripping characteristic C, residual current type AC 30 mA, breaking capacity 10 kA (EN 60898) / 20 kA (IEC 60947-2).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-1LB20 specifications
ParameterValue
Poles2
Depth77 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

The Siemens 5SU1354-1LB20 is a SENTRON RCBO (residual current circuit breaker with overcurrent protection) in a 2-pole 1P+N configuration, rated 20 A with a C tripping characteristic and 30 mA AC residual current sensitivity.

The 30 mA AC residual current type catches sinusoidal earth faults only — not pulsating DC or smooth DC, so it's correct for general-purpose circuits but not for variable-speed drives or EV chargers that generate DC fault content. Rated current derates with ambient temperature: 20 A at 30 °C, 18.8 A at 40 °C, 14.6 A at 70 °C. In a crowded enclosure running warm, the actual continuous load should be sized against the derated figure, not the 20 A label. That matters in industrial panels where equipment start-up transients are routine.

Snaps onto DIN rail in any orientation.

MPN
5SU1354-1LB20