Skip to main content
Siemens 5SU9356-7KM40

Siemens SENTRON 5SU9356-7KM40 RCD-operated circuit breaker,

MPN 5SU9356-7KM40

Siemens SENTRON 5SU9356-7KM40, RCBO, 40 A, 30 mA, type A, 1P+N, 6 kA (EN 60898), 10 kA (IEC 60947-2), characteristic C, 2 MW, halogen-free.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU9356-7KM40 specifications
ParameterValue
Poles2
Temp operating max45 °C
Temp operating min-25 °C
Depth77 mm
Width36 mm
Height90 mm

Product details

The Siemens SENTRON 5SU9356-7KM40 is an RCD-operated circuit breaker (RCBO) combining overcurrent protection and residual current detection in a single 2-module (36 mm wide) package. The type A residual current detection covers pulsating DC fault currents, common on single-phase electronics and rectified loads.

Breaking capacity and standards

Overvoltage category III confirms suitability for fixed installation downstream of the utility meter.

Thermal derating and conductor sizing

Rated current of 40 A at 30 °C derates to 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, and 32.4 A at 55 °C. In a 40 °C panel — typical for enclosed distribution boards — the effective continuous current is 37.6 A, so size the downstream load accordingly.

Mounting position any, supply feed either top or bottom. IP20 with connected conductors in an installed distribution board — standard for enclosed panel use. Halogen-free and silicon-free construction suits environments sensitive to corrosive off-gassing (data centers, medical facilities).

MPN
5SU9356-7KM40