Siemens 5SU9404-1KK06

Siemens 5SU9404-1KK06 SENTRON RCBO, 6 A, 10 kA, Type C, 1P+N

MPN 5SU9404-1KK06

Siemens SENTRON 5SU9404-1KK06, RCD-operated circuit breaker, 6 A rated current, 10 kA breaking capacity, Type C characteristic, 1P+N, 18 mm wide.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU9404-1KK06 specifications
ParameterValue
Poles2
Temp operating max45 °C
Temp operating min-25 °C
Depth77 mm
Width18 mm
Height125 mm

Product details

The Siemens 5SU9404-1KK06 is a 1P+N RCD-operated circuit breaker (RCBO) from the SENTRON 5SU9 series, combining overcurrent protection and residual current detection in a single 18 mm wide module. The integrated RCD trips on AC fault currents, so it's suited for circuits where both short-circuit and earth-fault protection are needed in one device. The 10 kA rating is typical for sub-distribution boards in commercial or light industrial panels.

Thermal derating and conductor sizing

The 6 A rating holds at 30 °C ambient; at 40 °C it derates to 5.64 A, at 45 °C to 5.46 A, at 50 °C to 5.22 A, and at 55 °C to 4.86 A.

Halogen-free and silicon-free construction.