Skip to main content
Siemens 5SY4205-5

Siemens 5SY4205-5 SENTRON MCB, 2-Pole, 0.5 A, Char A

MPN 5SY4205-5
Active

Siemens SENTRON miniature circuit breaker, 5SY4205-5, 2-pole, 0.5 A, tripping characteristic A, 10 kA per EN 60898, 35 kA per IEC 60947-2, 15 kA DC, 5 kA UL 1077/CSA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4205-5 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Breaking capacity and approvals

Rated breaking capacity hits 10 kA per EN 60898, 35 kA per IEC 60947-2, 15 kA at DC per IEC 60947-2, and 5 kA per UL 1077 and CSA C22.2 No. 235 — so it covers both residential-panel and industrial-distribution fault levels, plus DC circuits in control panels or battery-backed loads.

Thermal derating and environment

At 35 °C the breaker holds its full 0.5 A rating; at 45 °C it derates to 0.45 A, at 50 °C to 0.44 A, at 55 °C to 0.42 A, and at 60 °C to 0.4 A. Ambient range spans -40 °C to 75 °C, with humidity limits of 95 % up to 55 °C, 55 % up to 70 °C, and 35 % up to 75 °C. That wide range fits unheated enclosures or outdoor cabinets.

MPN
5SY4205-5