The 16 A rating holds at 35 °C ambient; above that, the breaker derates linearly to 12.86 A at 60 °C, so if your panel runs hot you need to account for that in your load calculation. The dual breaking capacity rating matters for selectivity: 10 kA under EN 60898 covers the residential/commercial standard, while the 20 kA under IEC 60947-2 gives you headroom for industrial fault levels. That 20 kA figure is what you'd use for SCCR coordination in a control panel feeding downstream contactors or drives.

Siemens 5SY4216-7KK11 SENTRON MCB, 2P C16, 10kA/20kA
MPN 5SY4216-7KK11
Siemens SENTRON 5SY4216-7KK11, 2-pole miniature circuit breaker, C16 characteristic, 10 kA (EN 60898) / 20 kA (IEC 60947-2), IP20, -40 to 75 °C, railway design.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| IP rating | IP20 |
| Mounting | Quick assembly system |
| Temp operating max | 75 °C |
| Temp operating min | 55 °C |
| Depth | 76 mm |
| Width | 36 mm |
| Height | 90 mm |
| Energy limitation class | 3 |
Product details
MPN
5SY4216-7KK11