Skip to main content
Siemens 5SY4263-6KK11

Siemens 5SY4263-6KK11 SENTRON MCB, 2P B-curve 63 A, 10kA EN

MPN 5SY4263-6KK11

Siemens SENTRON miniature circuit breaker, 5SY4263-6KK11, 2-pole, B tripping characteristic, 63 A rated current, 10 kA breaking capacity per EN 60898, 15 kA per IEC 60947-2, for railway applications.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4263-6KK11 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

The 63 A rating at 35 °C is the baseline; the breaker must be derated as ambient temperature rises — 59.16 A at 40 °C, 57.14 A at 45 °C, 55.06 A at 50 °C, 52.92 A at 55 °C, and 50.65 A at 60 °C. B-curve (trips at 3–5× In) is standard for resistive and general-purpose loads — lighting, control transformers, small heaters. It avoids nuisance trips from inrush on motor circuits; for motor-starting duty, a C-curve would be more typical, but B-curve is correct for the listed railway and mechanical-engineering applications. The 2-pole form (2P) isolates both phase and neutral in single-phase AC circuits.

The combined terminal at top and bottom accepts conductors without separate busbar links.

MPN
5SY4263-6KK11