Skip to main content
Siemens 5SY4408-8CV

Siemens 5SY4408-8CV MCB, 15kA Icu 400V 4P D8

MPN 5SY4408-8CV

Siemens 5SY4408-8CV, MCB Icu=15kA 400V 4P D8.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Product details

What the ratings mean for fit

The Siemens 5SY4408-8CV is a 4-pole miniature circuit breaker (MCB) with a D8 tripping characteristic and a rated ultimate short-circuit breaking capacity (Icu) of 15 kA at 400 V AC. The D-curve (8× to 14× In) is sized for loads with high inrush current — motor starters, transformers, or capacitive banks — where a B or C curve would nuisance-trip on startup. The 15 kA Icu at 400 V means this breaker can safely interrupt a fault current up to that level without welding its contacts or cascading failure upstream; that figure governs the SCCR (short-circuit current rating) of the downstream panel section.

Deployment context

This MCB snaps onto a standard 35 mm DIN rail inside a panel enclosure. The 4-pole format (3 poles + switched neutral) is typical for three-phase four-wire systems (TN-S or TN-C-S) where the neutral requires overcurrent protection. The D8 curve and 15 kA Icu suit it for motor control centers or distribution sub-panels feeding industrial loads with high inrush.