Skip to main content
Siemens 5SY5116-6CC12

Siemens SENTRON 5SY5116-6CC12 MCB, B-16 A, 1P DC, 10 kA

MPN 5SY5116-6CC12

Siemens SENTRON 5SY5116-6CC12, DC miniature circuit breaker, 1-pole, B characteristic, 16 A at 35 °C, 250 V DC max, 10 kA, railway design.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY5116-6CC12 specifications
ParameterValue
Poles1
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width18 mm
Height90 mm

Product details

At 16 A it protects a 3.8 kW DC load at 250 V (resistive). The single-pole construction switches the positive leg only; neutral is not switched, so the breaker must be installed in the ungrounded conductor per the polarity marking on the device. Temperature derating is significant: at 40 °C the rating drops to 15.1 A, at 50 °C to 14.16 A, and at 60 °C to 13.14 A. If the panel ambient runs 50 °C, size for 14 A continuous load, not 16 A. The humidity envelope caps at 95% RH up to 55 °C, then derates to 35% RH at 75 °C — relevant for unventilated enclosures in humid tunnels or washdown areas.

MPN