Skip to main content
Siemens 5SY5202-6

Siemens 5SY5202-6 SENTRON MCB, 2P B-Curve, 10 kA, 36 mm

MPN 5SY5202-6
Active

Siemens SENTRON 5SY5 series, miniature circuit breaker, 2-pole B-curve, 10 kA (EN 60898) / 15 kA DC (IEC 60947-2), 36 mm width, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY5202-6 specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

B-curve trip and breaking capacity — what they mean for the panel

The Siemens 5SY5202-6 is a 2-pole miniature circuit breaker from the SENTRON 5SY5 series, carrying a B-curve tripping characteristic. That means the magnetic trip operates at 3 to 5 times rated current — it's the right choice for resistive and general-purpose loads where inrush is modest, not for motor-starting or transformer primaries that would nuisance-trip a B-curve. The interrupting rating is 10 kA per EN 60898 and 15 kA at DC per IEC 60947-2, so it handles fault currents up to those levels without cascading upstream. The 36 mm width takes two modular-width units on the DIN rail — standard for a 2-pole MCB in European-style panels.

Panel fit and environmental limits

Mounts in any position on a DIN rail via the quick-assembly system. Depth is 76 mm, installation depth 70 mm — that's the dimension that matters for enclosure depth clearance. IP20 with connected conductors means it's protected against finger contact but not against moisture; keep it inside a rated enclosure. Ambient range runs from -40 °C to 75 °C, so it's fine in unheated electrical rooms or outdoor-rated cabinets. Pollution degree 3 and overvoltage category III — suitable for fixed installations with conductive pollution, typical of industrial panels.

Approvals and compliance documentation

Rated to IEC / EN 60898-2 and UL1077 — the dual standard covers both IEC and North American acceptance for supplementary protection. Halogen-free and silicon-free construction, which matters for outgassing-sensitive environments like clean rooms or sealed enclosures with electronics. The sealable design allows the installer to lock the toggle position after commissioning — useful for tamper-proofing in accessible panels.

MPN
5SY5202-6