It carries a C-curve trip characteristic, meaning it tolerates brief inrush currents up to 5–10× rated current before tripping — suited for moderate inductive or capacitive loads where nuisance tripping on energization must be avoided. At 35 °C ambient, it is rated 4 A; derate to 3.2 A at 55 °C and 3.01 A at 60 °C, so factor the enclosure temperature into your BOM line. Breaking capacity is 10 kA at 440 V DC per IEC 60947-2, with a maximum operating voltage of 500 V DC. This SCCR covers most auxiliary DC bus faults in traction or signaling panels without cascading upstream.

Siemens 5SY5204-7CC11 SENTRON MCB, 2P C-curve 4 A DC, 10 kA
MPN 5SY5204-7CC11
Siemens SENTRON 5SY5204-7CC11, 2-pole miniature circuit breaker, C-curve, 4 A (35 °C), 440 V DC, 10 kA breaking capacity per IEC 60947-2, for railway applications.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| IP rating | IP20 |
| Mounting | Quick assembly system |
| Temp operating max | 75 °C |
| Temp operating min | 55 °C |
| Depth | 76 mm |
| Width | 36 mm |
| Height | 90 mm |
Product details
5SY5204-7CC11 Datasheet
MPN
5SY5204-7CC11