Skip to main content
Siemens 5SY5210-6CC

Siemens SENTRON 5SY5210-6CC MCB, 10A B-Curve, 2P, DC 440V

MPN 5SY5210-6CC

Siemens SENTRON 5SY5210-6CC, miniature circuit breaker, 2-pole, B characteristic, 10 A at 35 °C, 10 kA DC at 440 V, 2 MW units, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY5210-6CC specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm

Product details

Siemens SENTRON 5SY5210-6CC — B-Curve 10 A DC MCB

This is an active-production part, specified for panel building and industrial control where selective coordination and reliable overcurrent protection are required.

DC Ratings and Breaking Capacity

This makes it suitable for DC bus protection in drives, UPS systems, or solar combiner boxes where fault currents can reach that level. The B-curve (3-5 In) trips fast on moderate overloads, so it pairs well with resistive or electronic loads that don't draw high inrush.

Rated current derates with ambient temperature: 9.32 A at 40 °C, 8.96 A at 45 °C, 8.58 A at 50 °C, and 8.19 A at 55 °C. The device operates across -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, 55% up to 70 °C, and 35% at 75 °C. This wide range covers unheated enclosures in cold climates and hot cabinet interiors near transformers or drives.

IP20 with connected conductors; touch protection is built in. Sealable for tamper-proofing in metering or critical circuits.

Construction and Compliance

Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5-25 Hz, 50 m/s² at 25-150 Hz. Combined terminals on top and bottom simplify busbar and cable connections. No neutral conductor switching — this is a 2-pole device for DC or phase + phase protection. Designation per IEC 81346-2 and DIN EN 61346-2 is F (protective device).

Marked as current-production. No official successor has been issued — this remains the active order code for new builds and spares.

MPN
5SY5210-6CC