Skip to main content
Siemens 5SY5225-7CC

Siemens 5SY5225-7CC SENTRON MCB, 2P C-curve 25 A, 10 kA DC

MPN 5SY5225-7CC

Siemens SENTRON 5SY5225-7CC miniature circuit breaker, 2-pole C-curve, 25 A at 35 °C, 10 kA DC at 440 V, 2 MW.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY5225-7CC specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm

Product details

The C curve means it handles moderate inrush — typical for motor starters, small transformers, and lighting banks in industrial panels — without nuisance trips on startup. At 40 °C the continuous rating derates to 23.3 A, at 50 °C to 21.45 A — so if your panel ambient runs warm, size the load against the derated number, not the 35 °C headline.

Panel integration

IP20 with connected conductors — fine for enclosed industrial panels, not for wet washdown zones.

Rated for ambient temperatures from -40 °C to 75 °C, with humidity limits per the spec (max 95% at 55 °C, derating to 35% at 75 °C). Halogen-free and silicon-free construction. Vibration resistance per IEC 60068-2-6: ±1 mm at 5 to 25 Hz, 50 m/s² at 25 to 150 Hz.

MPN
5SY5225-7CC