The 10 kA breaking capacity at 440 V DC (per IEC 60947-2) means this breaker can safely interrupt a DC fault current up to 10 kA without welding contacts or failing to clear — critical for DC bus or battery circuits where arc extinction is harder than in AC. The 2-pole configuration switches both lines in a DC circuit, providing full isolation. Terminals accept solid or stranded conductors from 0.75 to 35 mm², with a tightening torque of 2.5 to 3.5 N·m. The 36 mm width occupies 2 modular units on DIN rail.

Siemens 5SY5225-7CC11 SENTRON MCB, 2P C 25A DC 440V, Railway
MPN 5SY5225-7CC11
Siemens SENTRON 5SY5225-7CC11, miniature circuit breaker, 2-pole, C-curve, 25 A, 440 V DC / 400 V AC, 10 kA breaking capacity per IEC 60947-2, for railway applications.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| IP rating | IP20 |
| Mounting | Quick assembly system |
| Temp operating max | 70 °C |
| Temp operating min | -40 °C |
| Depth | 76 mm |
| Width | 36 mm |
| Height | 90 mm |
Product details
MPN
5SY5225-7CC11