The current rating is temperature-dependent: 63 A at 35 °C, derating to 59.47 A at 40 °C, 57.64 A at 45 °C, 55.76 A at 50 °C, 53.74 A at 55 °C, and 51.72 A at 60 °C. If your panel ambient runs at 50 °C, the breaker's continuous current limit is 55.76 A, not the 63 A on the label. That derating curve is the number to check against your load current, not the 35 °C figure.

Siemens 5SY5263-7CC11 SENTRON MCB, 2P, C-63 A DC, 10 kA
MPN 5SY5263-7CC11
Siemens SENTRON 5SY5263-7CC11, 2-pole miniature circuit breaker, C characteristic, 63 A at 35 °C DC, 10 kA interrupting capacity per IEC 60947-2, for railway applications.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| IP rating | IP20 |
| Mounting | Quick assembly system |
| Temp operating max | 75 °C |
| Temp operating min | 55 °C |
| Depth | 76 mm |
| Width | 36 mm |
| Height | 90 mm |
Product details
5SY5263-7CC11 Datasheet
MPN
5SY5263-7CC11