Skip to main content
Siemens 5SY6506-8CC

Siemens 5SY6506-8CC SENTRON MCB, D-curve 6A 1P+N, 6kA

MPN 5SY6506-8CC

Siemens SENTRON 5SY6506-8CC miniature circuit breaker, D tripping characteristic, 6 A rated current, 1P+N, 6 kA breaking capacity per EN 60898, 2 modular units wide.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY6506-8CC specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm

Product details

What the D-curve and 6 A rating mean for your panel

At 6 A, it protects downstream wiring and loads on a 1P+N (switched neutral) circuit, occupying 2 modular units (36 mm) on the DIN rail. Breaking capacity is 6 kA per EN 60898, and 5 kA per UL 1077 / CSA C22.2 No. 235 — sufficient for most commercial and light industrial distribution boards where the prospective fault current stays under those thresholds.

The 6 A rating holds at 35 °C. At 40 °C it derates to 5.51 A, at 45 °C to 5.25 A, at 50 °C to 4.97 A, and at 55 °C to 4.69 A. If your panel runs hot — near a drive or transformer — apply the derating curve to avoid nuisance tripping at rated load. The breaker survives ambient from -40 °C to 75 °C, with humidity limits of 95% up to 55 °C, tapering to 35% at 75 °C.

Combined terminals top and bottom simplify daisy-chaining busbars. The neutral conductor is switched internally (1P+N design), so no separate neutral pole is needed — saves a module width compared to a 2-pole breaker with unswitched neutral.

MPN
5SY6506-8CC