Siemens 6EP3343-0SA00-0AY0

Siemens 6EP3343-0SA00-0AY0 SITOP PSU8200, 10 A / 120 W

MPN 6EP3343-0SA00-0AY0
Active

Siemens SITOP PSU8200, 6EP3343-0SA00-0AY0, stabilized power supply, 10 A rated, 120 W output, input 85-264 V AC/DC, DIN rail mount.

$144.78 – $226.95 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6EP3343-0SA00-0AY0 specifications
ParameterValue
Fuse protection typeT 3.15 A (not accessible)
Voltage24 V
Power120 W
Frequency47 ... 63 Hz
Phases1-phase
IP ratingIP20
MountingSnaps onto DIN rail EN 60715 35x7.5/15
Depth135 mm
Width42 mm
Height125 mm
Efficiency88%

Product details

What this PSU delivers — and where it stops

The Siemens 6EP3343-0SA00-0AY0 is a SITOP PSU8200 stabilized power supply rated for 10 A continuous output at 120 W, with an input range of 85–264 V AC/DC (47–63 Hz). The 10 A figure is the full rated current across the 0–10 A range; below 110 V AC/DC the output power derates to 100 W max, so a 24 V rail pulling 10 A needs at least 110 V on the input side to hold full power. Galvanic isolation provides safety extra-low voltage (SELV) per EN 60950-1, which means the output is touch-safe and suitable for feeding control circuits, PLCs, and sensors without an additional isolation transformer. The unit snaps onto a DIN rail EN 60715 35×7.5/15 — standard panel mount, no drilling.

Mounting and thermal derating

In a 65 °C cabinet, that means 10 % derating — 108 W available instead of 120 W. Storage and transport range is –40 to +85 °C. IP20 protection — suitable for clean, dry control cabinets; not for washdown or outdoor use. The unit is ATEX and IECEx rated No, so it is not certified for explosive atmospheres. Clearance distances: top 50 mm, bottom 50 mm, left 0 mm, right 0 mm. That means zero side gap is acceptable — units can be mounted side-by-side without spacing, but 50 mm above and below must be free for convection airflow.

Approvals and feeder protection

UL/cULus-Listed under UL 508 and CSA C22.2 No. 107.1, File E197259 — accepted for North American panels. CE marked, EAC approved, C-Tick for Australia. Not CSA approved separately (covered by cULus), not DNV GL or FM registered, not NEC Class 2. Recommended feeder protection: a miniature circuit breaker 6–10 A, characteristic C. The maximum I²t value is 1 A²·s, which helps with coordination when sizing the upstream breaker.

Connections and wiring

Input terminals (, N, PE): one screw terminal each for 0.5–2.5 mm² single-core or finely stranded wire. Output terminals (+, –): two screw terminals each for the same wire range — useful for daisy-chaining to multiple loads without a separate distribution block.

Reliability and transient response

MTBF at 40 °C is 1 200 000 hours — roughly 137 years continuous. Typical response time (likely transient recovery or start-up delay) is 20 ms. Maximum leakage current is 3.5 mA, relevant for earth-leakage breaker coordination in sensitive installations.