Skip to main content
Siemens 3RW5076-2TB15

Siemens 3RW5076-2TB15 Soft Starter, 200 A, ATEX, 200-600 V

MPN 3RW5076-2TB15
Active

Siemens 3RW5076-2TB15 soft starter, 200 A minimum rated current, 200-600 VAC, ATEX and IECEx certified, trip class 10A/10E/20E per IEC 60947-4-2, PROFIBUS/Modbus/EtherNet/IP communications.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5076-2TB15 specifications
ParameterValue
Mountingscrew fixing
Depth282 mm
Width160 mm
Height230 mm
Trip classCLASS 10 A / 10E (preset) / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

200 A minimum and ATEX — what that means for a motor line

The 3RW5076-2TB15: The 200 A minimum current rating sets the floor for motor sizing — this soft starter handles motors drawing at least 200 A at full load, which typically corresponds to a 110-132 kW motor at 400 VAC depending on efficiency class. Below that threshold, the starter's internal current measurement and SCR firing lose resolution, so don't spec it for a 75 kW pump. ATEX and IECEx certification (both listed) means this unit can be installed in Zone 2 or Zone 22 hazardous areas without an external isolation barrier — the soft starter itself is certified for explosive atmospheres. That's a different procurement path than a standard soft starter that needs a downstream ATEX motor isolator.

Trip class and motor protection coordination

The class is field-selectable, not hard-coded. Voltage ramp and pump ramp down are both supported — the ramp profile reduces mechanical shock on start, and the pump ramp down extends the deceleration to prevent water hammer in pipeline systems. That's a feature set usually found on premium drives, not entry-level soft starters.

Fieldbus integration and panel fit

PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP are all native — no external gateway module needed for most plant networks. PROFIenergy is supported via the PROFINET communication module, which lets the soft starter participate in energy management shutdown sequences during production pauses. Mounting dimensions: 160 mm wide, 230 mm tall, 282 mm deep — screw fixing only, no DIN rail option. The 100 mm upward clearance and 75 mm downward clearance are minimums for airflow; pack them tighter and the 60°C ambient derating kicks in earlier. Side clearance is only 5 mm, so units can be ganged side-by-side in a multi-motor panel.

Active production and compliance documentation

The ATEX and IECEx certificates are separate documents from the CE declaration; request them from the supplier at RFQ time for your hazardous area dossier.

MPN
3RW5076-2TB15