Skip to main content
Siemens 5SU1354-1LB40

Siemens 5SU1354-1LB40 SENTRON RCBO, 40A C-Curve, 10kA, 2-Pol

MPN 5SU1354-1LB40

Siemens SENTRON 5SU1354-1LB40 RCBO, 40 A rated, C characteristic, 10 kA breaking capacity, 2-pole 1P+N, 2 MW wide, Type AC fault current.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-1LB40 specifications
ParameterValue
Poles2
Temp operating max55 °C
Temp operating min-25 °C
Depth77 mm
Width36 mm
Height90 mm

Product details

The 77 mm depth plus 70 mm installation depth means it sits flush in a typical distribution board without protruding past the gland plate. Mounting position is any, so no restriction on board orientation.

Thermal derating — what the numbers mean

At 40 °C it's 37.6 A; at 50 °C, 34.8 A; at 60 °C, 32.4 A; at 70 °C, 29.2 A. That's a roughly 27 % derating from 30 °C to 70 °C. If this RCBO sits in a crowded board next to other heat sources, the effective current capacity drops — plan the load accordingly.

Rated per EN 60898 for the 10 kA breaking capacity. Overvoltage category III, energy limiting class 3. The design code is 5SU1; the function letter per DIN EN 61346-2 and DIN EN 81346-2 is F (protective device). Type of fault current is AC (sine-wave residual current detection).

MPN
5SU1354-1LB40