Integration Note
The OPC-F1-PDP: The module plugs into the dedicated communication slot on the ECO pump drive. PROFIBUS DP runs at 12 Mbps maximum; set the station address via the DIP switches on the module face. The bus termination resistor is enabled by a jumper — one module at each end of the segment, as per PROFIBUS wiring practice. Shield the cable at the drive end only to avoid ground loops through the communication port.