Skip to main content
Siemens 5SL4106-0RC

Siemens Betagard 5SL4106-0RC MCB, 6A 1P Z-Char, 10kA

MPN 5SL4106-0RC

Siemens Betagard miniature circuit breaker, 5SL4106-0RC, 1-pole, 6 A, Z characteristic, 10 kA (EN 60898), 15 kA (IEC 60947-2).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL4106-0RC specifications
ParameterValue
Poles1
IP ratingIP20
Depth76 mm
Width18 mm
Height90 mm

Product details

Siemens Betagard 5SL4106-0RC — 6 A, Z-characteristic MCB

The Z curve trips between 2 and 3 times rated current — tighter than a B curve — so it catches semiconductor or control-transformer overloads before they cook the winding, but won't nuisance-trip on normal inrush from a 24 VDC supply. Rated voltage hits 440 V AC in single- or multi-phase operation, and DC rating maxes at 72 V — enough for most control-circuit rails.

Z-curve application and thermal derating

The Z characteristic (2–3× In trip band) is the main reason you'd pick this over a B or C curve: it protects circuits where even a brief 4× overload would damage downstream electronics — PLC power supplies, fieldbus couplers, instrumentation loops. At 30 °C ambient the breaker carries 6.5 A; at 50 °C it's back to 6 A; at 60 °C it's 5.7 A. Mounting position is unrestricted, so you can lay it sideways in a shallow gland box if needed.

Snap-on DIN-rail mount, 18 mm wide (1 MW). Sealable (padlockable toggle) for lockout/tagout. Halogen-free and silicon-free construction, which matters for clean-room or high-reliability environments where outgassing contaminates contacts or optics.

MPN