Skip to main content
Mitsubishi Electric AJ65BT-64RD4 — Digital Output Modules

Mitsubishi AJ65BT-64RD4 CC-Link RTD Input, 4 Ch Pt100/JPt100

MPNAJ65BT-64RD4

Mitsubishi Electric AJ65BT-64RD4 CC-Link RTD Input Unit, 4 Channels Pt100/JPt100, 0.025°C Resolution, 40 ms/Channel Conversion.

$828.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

AJ65BT-64RD4 key specifications
ParameterValue
Station typeRemote device station (Ver.1 remote device station)
Withstand voltageBetween power supply system batch and earth, power supply system batch and communication system batch, communication system batch and temperature input batch, between temperature input batch and ground: AC 500 V for 1 minute
Over voltage categoryII or less
Unit power supply voltageDC 24 V (DC 18 to 30 V)
Current0.17 A
Output current for temperature detection1 mA
Allowable momentary power failure time1 ms
Communication cableCC-Link dedicated cable
Installation locationIn the control panel
External wiring connection methodCommunication unit, Unit power supply unit: 7 points 2-piece terminal block (M3.5 screw) I / O section: 27 points 2 piece terminal block (M3.5 screw)
Operating temperature20 ° C or less, 30 ° C or more : ± 0.25%
Storage ambient temperature-20 to 75 ° C

All specifications

AJ65BT-64RD4 additional specifications
ParameterValue
Operating ambient temperature0 to 55 ° C
Measurement temperature range pt 100-180 to 600 ° C
Overall accuracy (accuracy with respect to maximum value) ambient temperature25 ± 5 ° C : ± 0.1%
Pollution degree2 or less
Storage ambient humidity10 to 90% RH, non condensing
Ambient operating humidity10 to 90% RH, non condensing
When there is continuous vibrationFrequency: 5 to 8.4 Hz, Amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Acceleration: 4.9 m / s 2
Depth63 mm
Width151.9 mm
Shipping weight1.4 Kg
External dimensions height65 mm
Mass0.38 Kg
JPt 100-180 to 600 ° C
Resolution0.025 °C
Use elevation0 to 2000 m
Use atmosphereNo corrosive gas
Conversion speed40 ms / channel
Measuring method4 wire type
Impact resistanceMeets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)
Insulation methodBetween platinum resistance temperature detector input and CC-Link transmission system: Photocoupler isolation Channel to non-insulation
Channels4 channels
Estimated lead timeUsually ships in 1 - 10 working days.
Insulation resistanceBetween power supply system batch and earth, power supply system batch and communication system batch, between communication system batch and temperature input batch, between temperature input batch and ground: 500 MV with insulation resistance meter 10 MΩ or more
Number of occupied stations4 stations
Usable resistance temperature detectorPt 100, JPt 100
Digital output temperature measurement value16-bit signed binary (-1800 to 6000: value to the first decimal place X 10 times) 32-bit signed binary (-180000 to 600000: value up to the third decimal place X 1000 times)

Product details

CC-Link temperature slice for Pt100/JPt100

The AJ65BT-64RD4 is a 4-channel RTD input module that reads Pt100 or JPt100 sensors over a CC-Link remote device station bus. Resolution runs 0.025°C per count, conversion speed is 40 ms per channel. It uses a 4-wire measuring method for lead compensation; output current for temperature detection is 1 mA.

Width 151.9 mm, depth 63 mm, height 65 mm. Operates in control panels (IP2x or better), ambient 0–55 °C, 10–90% RH non-condensing. Pollution degree 2, overvoltage category II. Power draw is 0.17 A from the 24 V DC unit supply. Communication uses CC-Link dedicated cable; the module occupies 4 stations on the bus.

Frequently asked questions

What is the listed mass of the AJ65BT-64RD4?

The unit mass is 0.38 kg.

MPN
AJ65BT-64RD4