Skip to main content
Mitsubishi Electric AJ65BT-64RD4

Mitsubishi AJ65BT-64RD4 CC-Link RTD Input, 4 Ch Pt100/JPt100

MPN AJ65BT-64RD4

Mitsubishi Electric AJ65BT-64RD4 CC-Link RTD Input Unit, 4 Channels Pt100/JPt100, 0.025°C Resolution, 40 ms/Channel Conversion.

$828.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

AJ65BT-64RD4 specifications
ParameterValue
Current0.17 A
Installation locationIn the control panel
Temp storage max75 °C
Temp storage min-20 °C
Temp operating max30 °C
Temp operating min20 °C
Pollution degree2 or less
Depth63 mm
Width151.9 mm
Channels4 channels
Measuring method4 wire type
Digital output temperature measurement value16-bit signed binary (-1800 to 6000: value to the first decimal place X 10 times) 32-bit signed binary (-180000 to 600000: value up to the third decimal place X 1000 times)

Product details

CC-Link temperature slice for Pt100/JPt100

The AJ65BT-64RD4 is a 4-channel RTD input module that reads Pt100 or JPt100 sensors over a CC-Link remote device station bus. Resolution runs 0.025°C per count, conversion speed is 40 ms per channel. It uses a 4-wire measuring method for lead compensation; output current for temperature detection is 1 mA.

Width 151.9 mm, depth 63 mm, height 65 mm. Operates in control panels (IP2x or better), ambient 0–55 °C, 10–90% RH non-condensing. Pollution degree 2, overvoltage category II. Power draw is 0.17 A from the 24 V DC unit supply. Communication uses CC-Link dedicated cable; the module occupies 4 stations on the bus.

MPN