Mitsubishi AJ65BTB2-16DR Remote I/O Station, 8 In/8 Out, DC

MPNAJ65BTB2-16DR

Mitsubishi AJ65BTB2-16DR remote I/O station, 8-point DC input / 8-point relay output, rated 70 mA at 24 VDC, switching up to AC 250 V / DC 110 V.

$265.65 – $328.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

AJ65BTB2-16DR key specifications
ParameterValue
Station typeRemote I / O station
Input common type8 points / common (terminal trapezoid 2 wire type)
Withstand voltageBetween AC external terminal and ground: AC 1500 V 1 min DC external terminal Between ground and ground: AC 500 V 1 min
Rated input voltageDC 24 V (ripple ratio within 5%) (Allowable voltage range DC 19.2 to 28.8 V)
Over voltage categoryII or less
ON voltage (ON current)14 V or more / 3.5 mA or more
Maximum switching voltageAC 250V DC 110V
OFF voltage (OFF current)6 V or less / 1.7 mA or less
Unit power supply voltageDC 24 V (ripple ratio within 5%) (allowable voltage range DC 15.6 to 28.8 V)
Rated switching voltage (current)DC 24 V 2A (resistance load) / 1 point, AC 240 V 2 A (cos φ = 1) / 1 point, 8 A / 1 common
Output section external power supply voltageDC 24 V ± 10% (ripple voltage 4 V pp or less)
Current70 mA or less (TYP. At 24 VDC)

All specifications

AJ65BTB2-16DR additional specifications
ParameterValue
Rated input currentAbout 7 mA
Maximum switching frequency3600 times / hour
Installation locationIn the control panel
External wiring connection methodCommunication part, Unit power supply part: 7 points 2 piece terminal block (M3.5 screw) I / O power supply part, input / output part: 37 points 2 piece terminal block (M3.5 screw)
Input response time OFF → ON10 ms or less
Output response time OFF → ON10 ms or less
Storage ambient temperature-20 to 75 ° C
Operating ambient temperature0 to 55 ° C
Pollution degree2 or less
Storage ambient humidity10 to 90% RH, non condensing
Ambient operating humidity10 to 90% RH, non condensing
When there is continuous vibrationFrequency: 5 to 8.4 Hz, One amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m / s 2
Depth46 mm
Width197.4 mm
Shipping weight1.4 Kg
External dimensions height65 mm
Mass0.43 Kg
ElectricalRated switching voltage . current load: 100,000 times or more AC 200 V 1.5 A, AC 240 V 1A (COS φ = 0.7): 100 thousand times or more AC 200 V 1A, AC 240 V 0.5 A (COS φ = 0.35): 100,000 times or more DC 24 V 1A, DC 100 V 0.1 A L / R = 7 ms): 100 thousand times or more
ON → OFF12 ms or less
Input formatDC input (plus common / minus common common type)
Use elevation0 to 2000 m
Use atmosphereNo corrosive gas
Input resistanceAbout 3.3 kΩ
Impact resistanceMeets JIS B 3502, IEC 61131-2 (147 m / s 2 , 3 times in each of X, Y and Z directions)
Estimated lead timeUsually ships in 1 - 10 working days.
Lifespan mechanicalOver 20 million times
Output common method8 points / common (terminal trapezoid 2 wire type)
Insulation resistanceAC external terminal all together and ground, DC external terminal collective to ground: 500 MV DC insulation resistance meter 10 MΩ or more
Input isolation methodPhotocoupler isolation
Number of input points8 points
Number of output points8 points
Output isolation methodPhotocoupler isolation
Number of occupied stations1 station
Minimum opening (closing load)DC 5 V 1 mA
Maximum number of simultaneous input points100%

Product details

What it is for the line-down swap

When a remote rack goes dark at 2am, this is the Mitsubishi AJ65BTB2-16DR you're after. It's an 8-in / 8-out remote I/O station that talks on the MELSEC network. Draws 70 mA typical from the 24 VDC bus. Inputs are sink/source configurable, plus common. Outputs are relay, rated for AC 250 V or DC 110 V at up to 1.5 A resistive. Photo-isolated both sides. The spec says 3600 cycles per hour max, so don't hammer it faster than that.

Panel fit notes

Mounts inside the control panel on a DIN rail (depth 46 mm, width 197.4 mm, height 65 mm). Accepts 24 VDC supply with 15.6 to 28.8 V range. Inputs consume about 7 mA each at 24 V. Output common per 8 points, terminal block style.

Ordering this for a BOM

Available through our network; we quote to order. No cross-reference needed — it's a current-production Mitsubishi part. Ensure your panel's overvoltage category is II or lower and pollution degree 2 or less per the spec.

Frequently asked questions

What is the mass and current draw of AJ65BTB2-16DR?

Mass is 0.43 Kg, and typical current draw is 70 mA at 24 VDC.