Skip to main content
Siemens 3RK4320-3NR51-0BA0

Siemens 3RK4320-3NR51-0BA0 SIRIUS Motor Starter, CLASS 10

MPN 3RK4320-3NR51-0BA0

Siemens SIRIUS motor starter MCU for AS-Interface, 3RK4320-3NR51-0BA0, direct starter design, CLASS 10 thermal bimetal protection, rated 10 A at AC-3 400 V, IP55 enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RK4320-3NR51-0BA0 specifications
ParameterValue
IP ratingIP55
Temp operating max35 °C
Temp operating min-25 °C
Depth145 mm
Width182 mm
Height220 mm
Trip classCLASS 10

Product details

What this SIRIUS motor starter is

It is an electromechanical switching contact device with bimetal motor protection, meaning it combines a contactor and overload relay in one housing for a single motor branch. Operates on a 340 to 440 V AC main circuit and draws control supply from a 20.4 to 26.4 V DC bus. Supports 50/60 Hz line frequencies.

AS-Interface integration and enclosure

This starter communicates natively over AS-Interface (Actuator-Sensor Interface), the bit-level fieldbus common in material handling and assembly lines for wiring sensors and actuators back to a master without a full PROFIBUS or PROFINET backbone. It does not support PROFIBUS DP or PROFINET protocols — the AS-Interface link is the only bus interface. The IP55 enclosure (protection against dust ingress and water jets) suits it for installation in industrial environments where washdown or airborne particulates are a concern — think packaging lines, food processing zones, or machine tool enclosures.

Protection and ratings

The CLASS 10 bimetal overload relay tracks motor current via a thermal model and opens the circuit before winding damage occurs. Short-circuit protection is provided by upstream circuit breakers. Operating frequency is rated at 80 operations per hour maximum — this is not a high-duty-cycle starter for rapid reversing or jogging applications. The unit has three poles for the main current circuit and no integrated brake control outputs. It is a straightforward direct-on-line (DOL) starter — not suitable for star-delta or reversing configurations without external contactors.

MPN
3RK4320-3NR51-0BA0