Rated 400 V AC and 60 V DC, with an insulation voltage (Ui) of 440 V AC. Overvoltage category 3 and pollution degree 3 — standard for fixed industrial installations where transients are expected. The 2-pole design switches both line conductors; neutral is not switched. Protection class IP20 with connected conductors; IP40 in the handle range. Vibration resistance rated at 50 m/s² at 25 to 150 Hz and 60 m/s² at 35 Hz (4 s) — enough for machine-mounted panels near rotating equipment.

Siemens SENTRON 5SJ4205-8HG42 MCB, 2-Pole, D Curve, 10 kA
MPN 5SJ4205-8HG42
Active
Siemens SENTRON 5SJ4 series, 5SJ4205-8HG42 miniature circuit breaker, 2-pole, D tripping characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC, 2 modular width units.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Poles | 2 |
| Mounting | on standard mounting rail |
| Depth | 70 mm |
| Width | 36 mm |
| Height | 121 mm |
Product details
5SJ4205-8HG42 Datasheet
MPN
5SJ4205-8HG42