Siemens 5SL4250-8

Siemens 5SL4250-8 SENTRON MCB, 2P, 50 A, D Curve, 10 kA

MPN 5SL4250-8
Active

Siemens SENTRON 5SL4250-8, 2-pole miniature circuit breaker, D characteristic, 50 A rated at 30 °C, 10 kA breaking capacity per EN 60898 and IEC 60947-2, 400 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SL4250-8 specifications
ParameterValue
Poles2
IP ratingIP20
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

The 2-pole configuration (2P) switches both phase conductors; neutral conductor switching is not included, so the neutral bar remains continuous through the panel. Mounting position is unrestricted — vertical, horizontal, or inverted — which simplifies layout in crowded enclosures.

Thermal derating and ambient limits

At 40 °C the breaker must be derated to 46.19 A; at 45 °C to 44 A; at 55 °C to 39.81 A. These are per the manufacturer's published curve — panel builders should apply the derating factor for the enclosure's internal temperature rise, not the room ambient. Degree of pollution is 2 (non-conductive pollution that may become conductive due to condensation), which covers most indoor panel environments.

Dimensions are 76 mm depth, 36 mm width (2 MW), 90 mm height. Installation depth is 70 mm — the extra 6 mm accounts for the terminal screw clearance behind the DIN rail.

MPN