Skip to main content
Siemens 5SU1353-7KL40

Siemens 5SU1353-7KL40 SENTRON RCBO, 40 A, Type C, 4.5 kA

MPN 5SU1353-7KL40

Siemens SENTRON 5SU1 RCBO, 1P+N, 40 A rated current, tripping characteristic C, 4.5 kA breaking capacity, type A fault current, halogen-free.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1353-7KL40 specifications
ParameterValue
Poles2
Temp operating max55 °C
Temp operating min-25 °C
Depth77 mm
Width36 mm
Height90 mm

Product details

The Siemens 5SU1353-7KL40 is a SENTRON 5SU1 RCBO (residual current circuit breaker with overcurrent protection) combining a 40 A rated current, type C tripping characteristic, and a 4.5 kA breaking capacity per EN 60898 into a single 1P+N unit. It detects type A fault currents — pulsating DC superimposed on AC — which covers most modern electronic loads like switched-mode power supplies and variable-speed drives.

Above that, the device derates: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C, 32.4 A at 60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C. If the panel ambient runs at 50 °C, the effective limit is 34.8 A — not 40 A. The type C magnetic trip (5–10× In) handles moderate inrush from motor starters and transformers without nuisance tripping, while the 4.5 kA SCCR at 230/400 V AC is adequate for most final subcircuits in a building distribution board. Overvoltage category III (distribution-level) and energy limiting class 3 mean it limits let-through energy enough to protect downstream wiring and loads under short-circuit conditions. The test button requires a minimum of 195 V to operate correctly — verify line voltage before commissioning.

Accepts solid or stranded conductors from 0.75 mm² up to 35 mm² — enough for a 40 A circuit on 6–10 mm² copper. Supply can enter from either top or bottom, which simplifies busbar routing in a crowded enclosure. IP20 rated once the distribution board cover is installed and conductors are connected.

MPN
5SU1353-7KL40