Skip to main content
Schneider Electric A9KR13263 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9KR13263 Acti9 ID K RCCB, 63 A, 30 mA, 2

MPNA9KR13263
Obsolete

Schneider Electric Acti9 ID K, RCCB, 2P, 63 A, 30 mA, Type AC, 220-240 V AC, DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9KR13263 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9KR13263 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)220...240 V AC 50 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)440 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemGroup incomer
Electrical durabilityAC-1: 4000 cycles
Mechanical durability (operating cycles)5000 cycles
A9KR13263 — Identification
ParameterValue
Product nameActi9 ID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameID K
A9KR13263 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsBiconnect top or bottom 1...35 mm² rigid Biconnect top or bottom 1...25 mm² flexible
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height81 mm
Depth68 mm
A9KR13263 — Environmental
ParameterValue
Operating ambient temperature-5...55 °C
Storage ambient temperature-25...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9KR13263 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 SS 97:part 1

Product details

Product identity and compliance

It is rated at 63 A with a 30 mA earth-leakage sensitivity, Type AC, and operates at 220-240 V AC, 50 Hz. This RCCB is fully compliant with EN/IEC 61008-1 and SS 97:part 1, carrying a SAFETY Mark quality label. The voltage-independent residual current tripping technology means it will trip on earth fault even if the supply voltage is lost — a key distinction for installations where fault protection must not rely on the mains.

Neutral on the left, poles description 2P. The compact 81 mm height and 68 mm depth fit standard modular enclosures with IP40 protection; the device itself carries IP20. Terminals accept 1-35 mm² rigid or 1-25 mm² flexible cable (biconnect top or bottom). Wire stripping length is 14 mm; tightening torque 3.5 N.m. The toggle control provides clear visual indication of the contact position.

Electrical ratings and environment

Rated insulation voltage (Ui) is 440 V AC; rated operational voltage (Ue) is 220-240 V AC. The breaking and making capacity is rated at Idm 630 A and Im 630 A. Electrical durability is 4000 cycles under AC-1 duty; mechanical durability is 5000 cycles. The device is tropicalised to class 2 per IEC 60068-1, with a relative humidity rating of 95% at 55 °C. Storage temperature range is -25 to 85 °C. Pollution degree 2. It withstands 8/20 µs impulse currents up to 200 A per EN/IEC 61008-1.

Frequently asked questions

What are the key ratings of the A9KR13263?

It is a 2-pole RCCB rated at 63 A with 30 mA sensitivity, Type AC, for 220-240 V AC 50 Hz networks. It clips onto DIN rail and complies with EN/IEC 61008-1.

Where can I buy the A9KR13263?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9KR13263