Skip to main content
Schneider Electric A9R70463 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R70463 Acti9 iID K RCCB, 63 A, 30 mA, 4

MPNA9R70463
Obsolete

Schneider Electric Acti9 iID K, 4P RCCB, 63 A, 30 mA Type AC, 380-415 V AC, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R70463 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R70463 — Electrical Ratings
ParameterValue
Rated current (In)63 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9R70463 — Identification
ParameterValue
Product nameActi9 iID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID K
A9R70463 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminals top or bottom 1...35 mm² rigid Tunnel type terminals top or bottom 1...25 mm² flexible Tunnel type terminals top or bottom 1...25 mm² flexible with ferrule
Wire stripping length16 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height85 mm
Depth69 mm
A9R70463 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9R70463 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

The Schneider Electric A9R70463 is a 4-pole residual current circuit breaker (RCCB) from the Acti9 iID K series, rated at 63 A with 30 mA Type AC earth-leakage sensitivity.

The 4-pole (4P) configuration with neutral on the left handles three-phase + neutral networks. Rated operational voltage of 380-415 V AC matches standard European low-voltage distribution. Breaking capacity Idm/Im of 630 A covers the prospective fault current typical at the outgoer position in a domestic or small commercial DB. Voltage-independent tripping means the RCCB detects earth leakage and disconnects even if the phase voltage collapses — a safety advantage over electronic RCDs that need auxiliary power to trip. Instantaneous response (no time delay) provides fast disconnection for shock protection.

Tunnel terminals accept 1-35 mm² rigid or 1-25 mm² flexible cable; strip 16 mm and torque to 3.5 N.m. IP20 on the body, IP40 inside the modular enclosure — standard for enclosed distribution boards.

Frequently asked questions

Where can I buy A9R70463 and get a price?

The A9R70463 is sourced and quoted to order against an RFQ. Submit a request for quote to confirm current availability and pricing.

What are the key specifications of A9R70463?

The A9R70463 is a 4-pole RCCB rated at 63 A with 30 mA Type AC earth-leakage sensitivity, operating at 380-415 V AC 50/60 Hz. It clips onto DIN rail, is 8 modules wide (72 mm), and complies with EN/IEC 61008-1 and EN/IEC 61008-2-1.

What compliance documentation does Schneider provide for A9R70463?

The A9R70463 carries VDE quality label and complies with EN/IEC 61008-1 and EN/IEC 61008-2-1 standards. It is rated IP20/IP40 per IEC 60529.

MPN
A9R70463