Skip to main content
Schneider Electric A9R74225 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9R74225 Acti9 iID RCCB, 25 A, 300 mA, 2P

MPNA9R74225
Active

Schneider Electric Acti9 iID, RCCB, 2P, 25 A, 300 mA, Type AC, 220-240 V AC, DIN rail clip-on, IP20/IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9R74225 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R74225 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)220...240 V AC 50/60 Hz
Poles description2P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9R74225 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9R74225 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...35 mm² rigid Single terminal top or bottom 1...25 mm² flexible Single terminal top or bottom 1...25 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width36 mm
Height91 mm
Depth73.5 mm
A9R74225 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9R74225 — Approvals
ParameterValue
StandardsEN/IEC 61008-1

Product details

The Schneider Electric A9R74225 is an Acti9 iID residual current circuit breaker (RCCB) — a 2-pole, voltage-independent device rated for 25 A continuous load at 220-240 V AC, 50/60 Hz. Its 300 mA earth-leakage sensitivity (Type AC) catches sinusoidal AC fault currents, tripping instantaneously with no auxiliary supply needed. That voltage-independent design means it clears a ground fault even if the line voltage has collapsed — a real advantage in degraded supply conditions.

Clip-on mounting to DIN rail, 36 mm wide (4 x 9 mm pitches), 91 mm tall, 73.5 mm deep — slots into a standard modular enclosure alongside other Acti9 devices. IP20 on the body, IP40 inside the modular enclosure per IEC 60529.

Pollution degree 3 suits it for industrial control panels where conductive contamination is possible. The 8/20 µs impulse withstand of 250 A confirms it handles surge events without nuisance tripping.

Frequently asked questions

Where can I buy A9R74225 and how do I get a price?

The A9R74225 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability confirmation at quote time.

What is A9R74225's listed depth?

The A9R74225 has a depth of 73.5 mm, fitting standard modular enclosures on DIN rail.

What is A9R74225's listed range?

The A9R74225 belongs to the Schneider Electric Acti9 range, specifically the iID series of residual current circuit breakers.

What compliance documentation does this brand provide for A9R74225?

The A9R74225 is designed and tested to EN/IEC 61008-1, with a rated impulse withstand voltage of 6 kV and insulation voltage of 500 V AC. Pollution degree 3 is specified for industrial environments.

MPN