Rated at 32 A with a C-curve trip characteristic, it breaks fault currents up to 6000 A Icn at 230 V AC 50 Hz per EN/IEC 61009-2-1.
The thermal-magnetic trip unit uses a bimetal for overload and a solenoid for short-circuit. Tropicalisation severity B per IEC 60068-2-30 for 28 days confirms it handles high-humidity sites without condensation corrosion.
Clip-on mounting to DIN rail (EN 60715). Cable entry from top or bottom; wire stripping length 14 mm, tightening torque 2 Nm. Neutral on the left side — check busbar orientation before assembly. Local signalling includes ON, OFF, fault trip LED, and arc fault diagnostic LED.