Skip to main content
Schneider Electric A9TDNC632 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9TDNC632 Acti9 iCV40 ARC, 32 A C-Curve R

MPNA9TDNC632
Active

Schneider Electric Acti9 Active iCV40 ARC RCBO, 32 A, C-curve, 1P+N, 6 kA breaking capacity, DIN rail mount, white (RAL 9003).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9TDNC632 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A-SI (Super Immunised)
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip LED arc fault diagnostic
A9TDNC632 — Electrical Ratings
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)250 V AC 50 Hz between phase and neutral
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII
Device location in systemOutgoer
Electrical durability10000 cycles 230 V AC 50 Hz
Mechanical durability (operating cycles)20000 cycles
A9TDNC632 — Identification
ParameterValue
Product nameActi9 Active iCV40 ARC
Product / component typeActive arc fault detection RCBO
Product range / familyActi9
Device short nameiCV40N ARC
A9TDNC632 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsTunnel type terminal 1...16 mm² rigid Tunnel type terminal 1...10 mm² flexible
Wire stripping length14 mm
Terminal tightening torque2 N.m
Width36 mm
Height91 mm
Depth73 mm
A9TDNC632 — Environmental
ParameterValue
Operating ambient temperature-25...50 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2 conforming to EN/IEC 62606
Relative humidity95 % at 55 °C
Operating altitude2000 m
TropicalisationSeverity B conforming to IEC 60068-2-30 for 28 d
A9TDNC632 — Approvals
ParameterValue
StandardsEN/IEC 62606 EN/IEC 61009-1 EN/IEC 61009-2-1

Product details

Rated at 32 A with a C-curve trip characteristic, it breaks fault currents up to 6000 A Icn at 230 V AC 50 Hz per EN/IEC 61009-2-1.

The thermal-magnetic trip unit uses a bimetal for overload and a solenoid for short-circuit. Tropicalisation severity B per IEC 60068-2-30 for 28 days confirms it handles high-humidity sites without condensation corrosion.

Clip-on mounting to DIN rail (EN 60715). Cable entry from top or bottom; wire stripping length 14 mm, tightening torque 2 Nm. Neutral on the left side — check busbar orientation before assembly. Local signalling includes ON, OFF, fault trip LED, and arc fault diagnostic LED.

Frequently asked questions

What are the key ratings of A9TDNC632?

32 A rated current, C-curve trip characteristic, 6 kA breaking capacity at 230 V AC, 1P+N poles, thermal-magnetic trip unit, limitation class 3.

Where can I buy A9TDNC632 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are listed here.

What compliance standards does A9TDNC632 meet?

Compliant with EN/IEC 62606 (arc fault detection), EN/IEC 61009-1 (RCBO general), and EN/IEC 61009-2-1 (RCBO functional). Overvoltage category III, pollution degree 2, tropicalisation severity B per IEC 60068-2-30.

MPN
A9TDNC632