Schneider Electric C080L35AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C080L35AFM ComPacT NS 800A 3P MCCB, 150 k

MPNC080L35AFM
Active

Schneider Electric ComPacT NS new generation, 800 A, 3P, MicroLogic 5.0 A electronic trip unit, 150 kA Icu at 415 V AC, fixed mount, manually operated, LCD display.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080L35AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C080L35AFM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C080L35AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 3000 cycles at 690 V In/2 3000 cycles at 440 V In 4000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C080L35AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C080L35AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C080L35AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C080L35AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

It's a 3-pole, 800 A frame, manually operated distribution breaker with a MicroLogic 5.0 A electronic trip unit.

The MicroLogic 5.0 A trip unit provides LSIG protection: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (earth-leakage — though this specific unit ships without earth-leakage protection). The electronic trip gives you adjustable curves, so you can coordinate downstream breakers. The 150 kA Icu at 415 V AC is the maximum short-circuit current the breaker can clear and still be usable afterward; at 500/525 V AC that drops to 100 kA Icu. The 20 W power loss is heat you need to vent in a closed panel — at 800 A continuous, that's real thermal load. The IP40 front face keeps tools and fingers out but isn't washdown-rated; this lives in a dry indoor switchboard.

Fixed mount on a backplate. Front connections both upside and downside. The 210 mm width and 327 mm height mean it fills a standard MCCB slot in a switchboard — check your cubicle cutout against those dimensions. The 147 mm depth is the body depth; add clearance for the front connections and the LCD display.

Frequently asked questions

How do I get current pricing and availability for C080L35AFM?

This part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What are the key ratings of C080L35AFM?

800 A trip rating at 50 °C, 150 kA Icu at 415 V AC, 3-pole, MicroLogic 5.0 A electronic trip unit with LSIG protection (earth-leakage not fitted on this unit). Complies with EN/IEC 60947-2.

What is the breaking capacity at different voltages?

150 kA Icu at 220/240 V AC, 150 kA Icu at 380/415 V AC, 130 kA Icu at 440 V AC, and 100 kA Icu at 500/525 V AC, all conforming to IEC 60947-2.

MPN